Obchod

AMR-OP40/03

134,78 excl. VAT

Temperature sensor, RS485, white/white, Time/Element

In stock

SKU: AMR-OP40RH/03
Categories: ,

  • measures ambient temperature

 

  • room temperature measurement
  • relative humidity measurement
  • indoor CO2 concentration measurement
  • 1× LED
  • MODBUS RTU / ARION (RS485) communication
  • ABB Time / Time Arbo design
  • user programming option

 

AMR-OP40RH

Temperature measurement Electronic
Measurement range -10 °C to 50 °C
Measurement accuracy ±0,5 °C
Communication  RS485 without galvanic isolation
Cover protection rate IP20
Mounting  On wall
Power supply 10 V DC to 30 V DC
Dimensions (w × h × d) (71 × 71 × 33) mm (depending on the frame type)

 

AMR-OP40RHC – temperature, relative humidity, COconcentration

Temperature measurement Electronic
Measurement range  -10 °C to 50 °C
Measurement accuracy ±0.5 °C
Relative humidity measurement Electronic
Measurement range 20 % to 80 %, non-condensing
Measurement accuracy ±3.5 %
CO2 concentration measurement NDIR
Measurement range 400 ppm to 2,000 ppm
Measurement accuracy ±50 ppm
Acoustic signalization Piezoconverter
Visual signalization LED
Communication RS485 (no GI)
Ingress protection rate IP30
Mounting On-wall
Power supply 10 V DC to 30 V DC
Dimensions (w × h × d) (71 × 71 × 33) mm (depending on the frame type)

 

Colour variants

Designation Colour design
AMR-OP4RH(C)/01 White/ice white, Time
AMR-OP4RH(C)/03 White/white, Time
AMR-OP4RH(C)/08 Titanium, Time
AMR-OP4RH(C)/32 Ancient silver, Time
AMR-OP4RH(C)/33 Champagne, Time
AMR-OP4RH(C)/34 Anthracite, Time
AMR-OP4RH(C)/36 Steel, Time
Document File
AMR-OP40RH/xx Data sheet amr-op40rhxx_d_en_100.pdf
Operation manual amr-op40rhxx_g_en_100.pdf
Drawing symbol amr-op40rhxx_s_en_100.zip
ePLAN macro amr-op40rhxx_se_en_100.zip
AMR-OP40RHC/xx ePLAN macro amr-op40rhcxx_se_en_100.zip
Data sheet amr-op40rhcxx_d_en_102.pdf
Operation manual amr-op40rhcxx_g_en_106.pdf
Drawing symbol amr-op40rhcxx_s_en_100.zip