AMR-OP71RH (C/P) – Wall-mounted controller
AMR-OP71RH is a design version of the AMR-OP70 controller. In terms of functions, both types of wall-mounted controllers are identical. The AMR-OP71 brings a new design of wall-mounted units with its platinum-coloured frame.
Apart from temperature and humidity measurement, the variant called AMR-OP71RHC also provides measurements of CO2 concentration in the air by means of a very reliable and stable sensor type NDIR. Furthermore, the unit is equipped with acoustic signalisation to alert the user about limit states of the CO2 concentration measured.
The AMR-OP71RHP variant provides direct access to the Poseidon 868 MHz network of wireless elements (sensors, switches, actuators). There is no need for a communication converter.
AMR-OP71
Control | Touch screen |
Display | Black-and-white graphic LCD |
Resolution | (64 × 132) pixels |
Display area | (58 × 38) mm |
Temperature measurement | Electronic |
Measurement range | -10 °C to 50 °C |
Measurement accuracy | ±0.5 °C |
RAM + RTC back-up | Yes (AMR-OP71B/01) |
Communication | RS485 (without GI) |
Ingress protection rate | IP20 |
Mounting | On-wall |
Power supply | 10 V DC to 30 V DC |
Dimensions (w × h × d) | (90 × 110 × 21) mm |
AMR-OP71C – temperature, CO2 concentration
Control | Touch screen |
Display | Black-and-white graphic LCD |
Resolution | (64 × 132) pixels |
Display area | (58 × 38) mm |
Temperature measurement | Electronic |
Measurement range | -10 °C to 50 °C |
Measurement accuracy | ±0.5 °C |
CO2 concentration measurement | NDIR |
Measurement range | 400 ppm to 3,000 ppm |
Measurement accuracy | ±150 ppm |
Acoustic signalization | Piezo buzzer (controlled by the application) |
Communication | RS485 (without GO) |
Ingress protection rate | IP20 |
Mounting | On-wall |
Power supply | 10 V DC to 30 V DC |
Dimensions (w × h × d) |
(90 × 110 × 21) mm |
Document | File | |
---|---|---|
AMR-OP71RH/xx | Data sheet | amr-op71rhxx_d_en_100.pdf |
Drawing symbol | amr-op71rhxx_s_en_100.zip | |
Operation manual | amr-op71rhxx_g_en_102.pdf | |
ePLAN macro | amr-op71rhxx_se_en_101.zip | |
AMR-OP71RHC/xx | Drawing symbol | amr-op71rhcxx_s_en_100.zip |
Data sheet | amr-op71rhcxx_d_en_100.pdf | |
Operation manual | amr-op71rhcxx_g_en_102.pdf | |
ePLAN macro | amr-op71rhcxx_se_en_101.zip | |
AMR-OP71RHP/xx | Data sheet | amr-op71rhpxx_d_en_100.pdf |
Drawing symbol | amr-op71rhpxx_s_en_100.zip | |
Operation manual | amr-op71rhpxx_g_en_102.pdf | |
ePLAN macro | amr-op71rhpxx_se_en_101.zip |